MSV-800 csb battery 2V800Ah Suitable for Telecom base station DC power backup, Optical access network central office backup, Microwave relay station DC supply, Telecom room 48V DC system
The CSB MSV-800 is a 2V 800Ah valve-regulated sealed lead-acid battery featuring AGM technology and pure lead construction, designed for high-capacity float standby power in telecom applications, with a design float life of up to 15 years.
Taobao store
WeChat procurement
Product Features
- Valve Regulated Lead Acid (VRLA) Battery
- Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%
- Pure Lead Construction and Proprietary Elements
- Designed for High Capacity Float Service Standby Power Applications
- Built in Accordance with IEC 60896-21/22:2004 and UL1989 Recognized (MH14533)
Application Scenarios
- Telecom base station DC power backup
- Optical access network central office backup
- Microwave relay station DC supply
- Telecom room 48V DC system
- Broadband access equipment backup power
- Mobile core network backup
Product parameters
- Model:MSV-800
- Voltage:2 Vdc
- Nominal Capacity:800 Ah @10hr-rate
- Ah Capacity:784.00 (8-Hr 1.75 VPC @ 25°C)
- Ah Capacity:820.00 (20-Hr 1.75 VPC @ 25°C)
- Ah Capacity:768.00 (8-Hr 1.80 VPC @ 25°C)
- Max. Charge Current:240.00 A
- Max. Discharge Current:4800 A
- Internal Resistance:0.38 mΩ
- Terminal Type:I4 thread copper alloy terminal to accept M8 bolt
- Terminal Torque:126±25 Kgf·cm / 109±22 Lbf·in / 12.3±2.5 N·m
- Container Material:Flame-retardant ABS (UL 94-V0)
- Weight:50.60 / 111.52 kg / lb.
- Length (L):373.0±2.5 / 14.69±0.10 mm / in
- Width (W):174.0±2.0 / 6.85±0.08 mm / in
- Height (H):339.0±2.5 / 13.15±0.10 mm / in
- Design Life:Up to 15 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
- Float Charging Voltage:2.21 ~ 2.25 Vdc/battery
- Equalizing Charging Voltage:2.35 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The CSB MSV-800 belongs to the MSV series and is a 2V VRLA-AGM valve-regulated sealed lead-acid battery. Its official application area is telecommunications, and the series is positioned for high-capacity, long-life standby power in large emergency and telecom scenarios. Its nominal capacity is 800Ah (1.80 VPC @25°C, 10hr-rate). At 25°C, the 20-hour rate (1.75 VPC) capacity is 820.00Ah, the 8-hour rate (1.75 VPC) is 784.00Ah, and the 8-hour rate (1.80 VPC) is 768.00Ah, allowing standby duration requirements to be matched under different discharge regimes.
The battery adopts a valve-regulated sealed lead-acid structure and absorbed glass mat AGM technology, with gas recombination efficiency of up to 99%. It is a maintenance-free design manufactured with pure lead construction and proprietary elements, suitable for high-capacity float standby power applications. The product is manufactured in accordance with IEC 60896-21/22:2004 and is recognized under UL1989 (MH14533). The case uses flame-retardant ABS material meeting UL 94-V0 requirements, helping ensure safe operation in environments such as equipment rooms and telecom sites.
In terms of electrical parameters, the MSV-800 has a nominal voltage of 2 Vdc, a maximum charge current of 240.00A, a maximum discharge current of 4800A, and an internal resistance of 0.38 mΩ. At 25°C, the float charge voltage is 2.21 to 2.25 Vdc/battery, and the equalizing charge voltage is 2.35 Vdc/battery. The terminal is an I4 threaded copper alloy terminal that accepts an M8 bolt, with a terminal torque of 126±25 Kgf·cm, 109±22 Lbf·in, or 12.3±2.5 N·m, facilitating reliable connections in telecom DC power systems.
In terms of dimensions and weight, the battery length is 373.0±2.5mm, width 174.0±2.0mm, height 339.0±2.5mm, and weight 50.60kg (111.52 lb.). It is a large-format 2V cell suitable for grouped installation in standby power systems in telecom equipment rooms. Its design life can reach 15 years under 25°C float service, and more than 12 years under the Eurobat (20°C) standard, placing it in the Very Long Life class, suitable for telecom and emergency power supply applications requiring long-term float standby.
In terms of operating temperature, the nominal temperature is 25°C (77°F), the discharge temperature range is -15°C to 50°C (5°F to 122°F), and the charge and storage temperature range is -15°C to 40°C (5°F to 104°F). In terms of self-discharge, capacity loss after 90 days of storage at 25°C is less than 10%. It can be stored for up to 6 months and must be fully charged before use; if the storage temperature is above 25°C, charging should be performed earlier to maintain battery condition.