HRL1280W csb battery 12V Suitable for Large data center UPS backup, Cloud computing center HVDC backup, Financial trading system UPS, Telecom hub UPS emergency protection
The CSB HRL1280W is an HRL Series 12V valve-regulated sealed lead-acid battery featuring AGM technology and pure lead construction, with a 15-minute rate nominal capacity of 80W, designed for high-rate float standby power such as data center UPS.
Taobao store
WeChat procurement
Product Features
- Valve Regulated Lead Acid (VRLA) Battery
- Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%
- Pure Lead Construction and Proprietary Elements
- Designed for High-Rate UPS, Float Service Standby Power Applications
- Built in Accordance with IEC 61056-1/2:2012 and UL1989 Recognized (MH14533)
Application Scenarios
- Large data center UPS backup
- Cloud computing center HVDC backup
- Financial trading system UPS
- Telecom hub UPS emergency protection
- Industrial automation UPS high-power backup
- Rail transit signal UPS backup
Product parameters
- Model:HRL1280W
- Voltage:12 Vdc
- Nominal Capacity:80W @15min-rate
- Watts per Cell:161.83 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:80.83 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:8.0 A
- Max. Discharge Current:300 A
- Short Circuit Current:723 A
- Internal Resistance:9.00 mΩ
- Terminal Type:I1 thread lead alloy terminal to accept M5 bolt
- Terminal Torque:30.4±6.1 Kgf·cm / 26.4±5.3 Lbf·in / 3.0±0.6 N·m
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:6.60 / 14.55 kg / lb.
- Length (L):181.0±2.0 / 7.13±0.08 mm / in
- Width (W):76.0±1.0 / 2.99±0.04 mm / in
- Height (H):165.0±2.0 / 6.50±0.08 mm / in
- Design Life:Up to 8 years in standby service at 25°C; Eurobat (20°C): 10-12 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The CSB HRL1280W belongs to the HRL Series, a product type of 6V and 12V top terminal valve-regulated sealed lead-acid batteries, featuring a valve-regulated sealed structure and absorbed glass mat (AGM) technology, with gas recombination efficiency up to 99%, and a maintenance-free design. This series is positioned as a long-life, high-rate UPS pure lead battery series, aimed at demanding high-power data center and UPS loads, with the official application area being data center uninterruptible power supplies.
In terms of electrical parameters, the HRL1280W has a voltage of 12 Vdc, and at 1.67 VPC, 25°C, the 15-minute rate nominal capacity is 80W; the 5-minute rate power is 161.83 W/cell, and the 15-minute rate power is 80.83 W/cell. The maximum charging current is 8.0 A, the maximum discharge current is 300 A, the short-circuit current is 723 A, and the internal resistance is 9.00 mΩ. The float charge voltage is 13.5 to 13.8 Vdc/battery (25°C), and the equalizing charge voltage is 14.4 to 15.0 Vdc/battery (25°C).
In terms of structure and dimensions, the battery length is 181.0±2.0 mm, width 76.0±1.0 mm, height 165.0±2.0 mm, and weight 6.60 kg. The terminal is an I1 threaded lead alloy terminal, accepting an M5 bolt, with a terminal torque of 30.4±6.1 Kgf·cm, 26.4±5.3 Lbf·in, or 3.0±0.6 N·m. The case material is ABS (UL 94-HB), and a flame-retardant 94-V0 version is available upon request.
In terms of operating temperature, the nominal temperature is 25°C, the discharge temperature range is -15°C to 50°C, and the charging and storage temperature range is -15°C to 40°C. Self-discharge is less than 10% after 90 days at 25°C, and it can be stored for up to 6 months at 25°C, requiring a full charge before use; if the storage temperature is above 25°C, it should be charged sooner. The design life can reach 8 years under float service at 25°C, and Eurobat (20°C) is 10 to 12 years standard commercial. The product is manufactured in accordance with IEC 61056-1/2:2012 and is UL1989 recognized (MH14533).